User Defined 240V-A Grid Standard
Parameter | Value | Description |
OV-G-V1 | 264V | Level 1 Phase to Phase over voltage trip set point |
OV-G-V1 - T | 1s | Duration of grid over voltage trip point |
OV-G-V2 | 288V | Level 2 Phase to Phase over voltage trip set point |
OV-G-V2 - T | .16s | Duration of grid over voltage trip point |
UN-G-V1 | 211V | Level 1 Phase to Phase under voltage trip set point |
UN-G-V1 - T | 2s | Duration of grid under voltage trip point |
UN-G-V2 | 144V | Level 2 Phase to Phase under voltage trip set point |
UN-G-V2 - T | .16s | Duration of grid under voltage trip point |
OV-G-F1 | 60.5Hz | Level 1 Grid over frequency trip set point |
OV-G-F1 - T | 2s | Duration of grid over frequency trip set point |
OV-G-F2 | 62Hz | Level 2 Grid over frequency trip set point |
OV-G-F2 - T | .16s | Duration of grid over frequency trip set point |
UN-G-F1 | 59.5Hz | Level 1 Grid under frequency trip set point |
UN-G-F1- T | 2s | Duration of grid under frequency trip set point |
UN-G-F2 | 57Hz | Level 2 Grid under frequency trip set point |
UN-G-F2 - T | .16s | Duration of grid under frequency trip set point |