User Defined 240V-A Grid Standard

User Defined 240V-A Grid Standard

ParameterValueDescription
OV-G-V1264VLevel 1 Phase to Phase over voltage trip set point
OV-G-V1 - T
1sDuration of grid over voltage trip point
OV-G-V2
288VLevel 2 Phase to Phase over voltage trip set point
OV-G-V2 - T
.16sDuration of grid over voltage trip point
UN-G-V1211VLevel 1 Phase to Phase under voltage trip set point
UN-G-V1 - T
2sDuration of grid under voltage trip point
UN-G-V2
144VLevel 2 Phase to Phase under voltage trip set point
UN-G-V2 - T
.16sDuration of grid under voltage trip point
OV-G-F160.5HzLevel 1 Grid over frequency trip set point
OV-G-F1 - T
2s    Duration of grid over frequency trip set point
OV-G-F2
62HzLevel 2 Grid over frequency trip set point
OV-G-F2 - T
.16sDuration of grid over frequency trip set point
UN-G-F159.5HzLevel 1 Grid under frequency trip set point
UN-G-F1- T
2sDuration of grid under frequency trip set point
UN-G-F2
57HzLevel 2 Grid under frequency trip set point
UN-G-F2 - T
.16sDuration of grid under frequency trip set point