Rule 21 Phase 1 July 26th Changes 1P and 3P

 Single Phase / Three Phase - Note Step 7 Differences 

 

Please follow all local safety standards 

 

This method of procedure has been created to assist all installers in setting the Ginlong Solis Inverters to comply with Rule 21 Phase 1 July 26th changes. This change can only be completed on all Ginlong Solis Rule 21 compliant inverters. For any questions please contact our service line at 866-438-8408. 

 

Step 1: Turn the inverter on with DC Voltage Only 

 

Step 2: Go to the Advanced Settings in the Menu 

 

 

Step 3: Grid On/OFF and set Grid to OFF 

 

 

Step 4: Go to STD. Mode Settings 

 

 

Step 5: Go to Working Mode Set 

 

 

Step 7 Single Phase: Set the settings as follows: 

  • V1 – 220 

  • V2 – 232 

  • V3 – 247 

  • V4 – 256 

  • Q1 – 30% - Default 

  • Q2 – 30% - Default 

Step 7 Three Phase: Set the settings as follows: 

  • V1 – 255 

  • V2 – 268 

  • V3 – 286 

  • V4 – 297 

  • Q1 – 30% - Default 

  • Q2 – 30% - Default 

 

 

Step 8: Hit Escape 

 

Step 9: Save and Send 

 

Step 10: Go to Grid On/OFF and turn the grid back on. 

 

Step 11: Complete your commissioning process. 

 

 