Single Phase / Three Phase - Note Step 7 Differences
Please follow all local safety standards
This method of procedure has been created to assist all installers in setting the Ginlong Solis Inverters to comply with Rule 21 Phase 1 July 26th changes. This change can only be completed on all Ginlong Solis Rule 21 compliant inverters. For any questions please contact our service line at 866-438-8408.
Step 1: Turn the inverter on with DC Voltage Only
Step 2: Go to the Advanced Settings in the Menu
Step 3: Grid On/OFF and set Grid to OFF
Step 4: Go to STD. Mode Settings
Step 5: Go to Working Mode Set
Step 7 Single Phase: Set the settings as follows:
V1 – 220
V2 – 232
V3 – 247
V4 – 256
Q1 – 30% - Default
Q2 – 30% - Default
Step 7 Three Phase: Set the settings as follows:
V1 – 255
V2 – 268
V3 – 286
V4 – 297
Q1 – 30% - Default
Q2 – 30% - Default
Step 8: Hit Escape
Step 9: Save and Send
Step 10: Go to Grid On/OFF and turn the grid back on.
Step 11: Complete your commissioning process.