OV-TEM Alarm

Created by Michael Allen, Modified on Thu, Sep 8, 2022 at 3:02 PM by Michael Allen

The OV-TEM alarm is displayed when the inverter detects high ambient temperature (greater than 60° C/140° F)

Troubleshooting steps:

  • Inspect the installation: check the fan and heatsink for obstructions
  • Is the inverter in direct sunshine? If so, it probably cannot dissipate heat quickly enough.
  • Measure the ambient temperature near the inverter and compare it with the temperature displayed in the Advanced Information menu (in Running Status)
  • If the temperature is above 60°C then the inverter will need to cool down before this alarm will go away
  • If the temperature displayed does not match the temperature measured, contact Solis Support

Was this article helpful?

That’s Great!

Thank you for your feedback

Sorry! We couldn't be helpful

Thank you for your feedback

Let us know how can we improve this article!

Select at least one of the reasons
CAPTCHA verification is required.

Feedback sent

We appreciate your effort and will try to fix the article