Solis Inverter Alarm Codes (Complete List)

This article serves as an overview of all Solis alarm codes. Please use it to quickly find the article that you need depending on the alarm code you are experiencing. 

For the Solis RHI-1P(5-10)K-HVES-5G-US (hybrid energy storage) inverter alarms, please scroll down and use the second chart.

Click or tap the Alarm Code/Issue name to see the troubleshooting guide specific to that issue


Alarm Code or IssuePossible Cause(s)Basic Troubleshooting Steps 
AFCI: an arc-fault is detected• Loose connection/termination
• Damaged PV module
• MLRSD failure/incompatibility

Test - DC switch OFF
• Check PV strings with a megger
• Plug one string in at a time to see which string causes arc-fault
• Check all connection points and modules with a thermal camera
No Information - Blank Screen• DC input voltage low/missing
• DC string polarity reversed
• Internal DC short - RMA
Test – DC switch OFF
• Check string polarity to make sure it is not reversed
• Check DC string voltages >120V Single, >350V three
Test – DC Switch ON
• Check DC string voltages again >120V Single, >350V three
• If DC voltage is “0” replace inverter - internal DC short - RMA
If DC voltages are all normal but inverter won't turn on - RMA
Inverter stuck displaying "Initializing"

• Inverter is waiting for the
driving signal from the DSP

• Contact Solis Support (RMA)
• Contact he inverter is not receiving a signal from the DSP board or it has a faulty internal power board
OV-G-V: AC voltage is over the limit 

• The wrong grid standard has been selected (must be US)

• The grid voltage is high

• The inverter is measuring the voltage as higher than it actually is

Test – DC switch OFF
• Check AC at the inverter
• If AC measures high, adjust upper limit with
permission from utility
Test – DC Switch ON, full power
• Check AC at inverter test points
• Compare with LCD
• If AC measures high, cables between inverter
and interconnect are too small
• Check ampacity and voltage drop calculations
UN-G-V: AC voltage is under the limit

• The wrong grid standard has been selected (must be US)

• The grid voltage is low

• The inverter is measuring the voltage as lower than it actually is

Test – DC switch OFF
• Check AC at the inverter test points
• If AC measures low, adjust lower limit with
permission from utility
• Check LCD voltage reading, may be a bad
measurement circuit
Test – DC Switch ON
• Check grid standard
• Replace inverter
OV-G-F: grid frequency is over the limit

• The wrong grid standard has been selected (must be US)

• The grid frequency is high

• The inverter is measuring the frequency as higher than it actually is

Test – DC switch OFF
• Check frequency at the inverter test points
• If frequency measures high, adjust upper
limit with permission from utility
• Check LCD reading, may be a bad
measurement circuit
Test – DC Switch ON
• Check grid standard
• Replace inverter
UN-G-F: grid frequency is under the limit

• The wrong grid standard has been selected (must be US)

• The grid frequency is low

• The inverter is measuring the frequency as lower than it actually is



Test – DC switch OFF
• Check frequency at the inverter test points
• If frequency measures low, adjust upper
limit with permission from utility
• Check LCD reading, may be a bad
measurement circuit
Test – DC Switch ON
• Check grid standard
• Replace inverter
NO-Grid: inverter does not detect any AC voltage• The AC switch/breaker is off
• The DC switch was turned on before the AC switch - sometimes this results in the inverter stuck displaying "No-Grid"
Potential Resolution: 
Turn the DC switch off and leave it off until the screen goes blank. Then turn on the AC switch followed by the DC switch. Wait to make sure the system begins generating after five minutes. If this does not work, proceed with the steps below.
Test – DC switch OFF
• Measure the AC voltage at the AC grid input terminals
• L1-L2, L1-L3, L2-L3, L1-GND, L2-GND, L3-GND
• Check the AC voltages found in the Information menu, if they do not match your multimeter - RMA (send a photo of this)
OV-DC: PV voltage is over the limit• PV string voltage is too high
• Internal DC voltage sensors are faulty
Test – DC switch OFF
• Check DC at the inverter test points
• If DCV is high, too many panels in the string
Test – DC Switch ON
• Check LCD reading, may be a bad
measurement circuit
• Replace inverter
OV-BUS: DC bus voltage is too high• Internal component failure is likely


Test
• Measure DC and AC voltages with a multimeter
• Compare with voltages found in the Information menu
• If multimeter and display voltages do not match - RMA
• If the values do match, ensure that they do not exceed the inverter specifications. If they do, reconfigure your PV strings to have lower voltage so that it is within spec
UN-BUS: DC bus voltage is too low• PV string voltage is too low
• Internal component failure is likely
Test
• Measure DC and AC voltages with a multimeter
• Compare with voltages found in the Information menu
• If multimeter and display voltages do not match - RMA
• If the values do match, ensure that they do not exceed the inverter specifications. If they do, reconfigure your PV strings to have lower voltage so that it is within spec
ILeak-PRO: current leakage to ground detectedAn exposed AC or DC conductor making contact with something metallic
A faulty PV module could be causing a leakage to ground
• See the guide - tap/click the link to be taken to it
Fan-Fail: an internal or an external fan has stopped working• A fan has become clogged with debris such as grass or a bug nest
• If the temperature is at or below freezing, a fan may have some ice build-up
• The fan may connection may be loose

Test - DC switch ON

  • Go to Advanced Settings > Fan Test > run the test
  • Watch the fans to ensure they all spin during the test
  • If one fan is not spinning then try to spin it with your fingers - if it spins with your fingers then remove the fan and swap it with a fan that was spinning 
  • Run the test again - if the fan still does not spin after the swap, then the fan is defective and needs to be replaced 
PID Repairing: low DC voltage or DSP issues• Low/no DC voltage with AC switched turned on
• Missing/corrupt DSP firmware
• Faulty DSP board
• Check the DC voltage - if it is lower than the startup voltage this is why PID Repairing is displayed - fix the DC voltage, then power-cycle the inverter
• If the DC voltage is normal and the DC switch is ON but PID Repairing is still displayed, see the article by clicking the link
GRID-INTF: harmonic distortion (line noise) on the AC-side • Could be inverter, the utility, or local nonlinear electrical equipment causing the noiseTest – With DC Switch OFF
• Measure AC voltage
• Test AC line for THD
• Test – With DC Switch ON
Test AC line for THD
• Multiple inverters/turn one off
• Impedance matching adjustment or box
• Internal damage
• Wire came loose in shipping  
DC-INTF: abnormality on the DC side of the system• Ground-fault 
• DC interference caused by a faulty internal component 
• DC interference caused by a faulty external component (such as module-level rapid shutdown equipment)
Test – With DC Switch OFF
  • Measure PV string voltage positive and negative to ground - if stable voltage then locate ground-fault
  • If using MLRSD with multiple strings, then run system with one string at a time only to isolate the source of the DC fault
  • If you only have one MLRSD string, disconnect all of the receivers and run the system with full Voc - if no fault is triggered then one of the receivers is defective
  • If there is no ground-fault or defective MLRSD receiver then the fault is likely internal - contact Solis Support
G-IMP• High grid impedance detectedUse the User-Define grid standard so you can adjust the protection limit if it is allowed by the utility
INI-FAULT:
Initialization
Protection    
• Master and Slave DSP
have different values
Reset Inverter
• DC switch OFF
• Wait until all lights/LCD turn off
• DC switch ON
• Replace inverter
OV-TEM: inverter internal temperature is too high
• Inverter detects high
ambient temperature >60C
Inspect installation
• Check heatsink for obstructions/ventilation
• Is inverter in direct sunshine
• Measure ambient temperature near inverter
• If temp is in range replace inverter
PV ISO-PRO: ground-fault detected on the DC side• Inverter detects low DC
insulation resistance - ground fault on one of the PV strings

Inspect installation
• Reset inverter
• Note weather conditions when alarm occurs
• Measure insulation resistance
• If normal, measure in SAME weather as alarm
• Physically check cables
• Replace inverter
IG-AD: grid current sampling failure

• Internal component failure

• Contact Solis Support (RMA)
LimByVg: power curtailed due to grid voltage

• Power is being curtailed because of the grid voltage being too high or too low 

• Inspect panel junction boxes
• Inspect cable connections
• Reset inverter
• Replace inverter
LimbyTem: power curtailed due to extreme temperature• Power is being curtailed because the internal temperature is too high or too low • Check the internal temperature of the inverter through Advanced Information > Running Status
• Temperature must be between -17°C and 40°C for 100% of max. power output (1.4°F and 104°F)
• Inverter will derate above/below those temperatures
Relay-PRO

• An inverter internal relay has malfunctioned 

• Power-cycle the inverter
• If the alarm persists, contact Solis Support (RMA)
DCinj-Fault• High DC injection current• Power-cycle the inverter
Softrun: inverter is running w/ relays open until the grid voltage & frequency is matched
• As the inverter starts up, it is common for the Softrun message to display
• If the inverter gets stuck displaying Softrun, please see the guide by following the link
IGFOL-FGrid Current Tracking ErrorRestart the inverter - if the alarm persists, RMA


For the RHI-1P(5-10)K-HVES-5G-US series, please use the chart below for any alarms not listed above - these alarms are unique to the hybrid inverter series and will not be seen on any other Solis inverter models. 

***Click or tap the Alarm Code name to see the on how to troubleshoot that specific alarm***

 

Alarm Codes and Issues for Solis RHI-1P(5-10)K-HVES-5G-US
Alarm Code or IssueFailure DescriptionSolution
AC OvercurrentHigh current demand from the backup loads or a faulty outletThere is too much draw on the backup loads panel > 25A reduce the current draw or install a 25A supply breaker so there is an OCPD in place - check to make sure no outlets are tripping
AC Transient over currentAC Transient OvercurrentCheck if the backup port is shorted, restart the inverter
LmtByPLmtOutput power reduced due to Export Power configurationOutput power is being limited because the system is currently set up for minimum export. Please see Export Power Set on how to change this if you want the system to be exporting power. 
LimByVgLimited by grid voltageIf Rule 21 is unnecessary, then set working mode to "NULL" but if Rule 21 is required, know that this code is designed to protect the inverter and is normal but if the code is given for long periods of time then it could mean there is an issue with the inverter or grid. 
IGBT-OV-IIGBT OvercurrentRestart the inverter
OV-IgTrGrid Transient OvercurrentRestart the inverter
OV-Vbatt-HBattery Hardware OvercurrentCheck if the battery is correctly connected or the battery contactor is disconnected, restart the battery, restart the inverter
OV-ILLCLLC Hardware OvercurrentRestart the inverter
OV-VbattBattery OvervoltageCheck if the battery overvoltage setting is reasonable, if the battery reaches its end of life
UN-VbattBattery UndervoltageCheck if the battery undervoltage setting is reasonable, if the battery reaches its end of life
DSP-B-FAULTSlave DSP Check ErrorRestart the inverter
NO-BatteryBattery Not ConnectedCheck if the battery is correctly connected or the battery contactor is disconnected, Restart the battery
OV-VbackupInverting OvervoltageRestart the inverter
Over-LoadBackup OverloadCheck if the backup port is shorted or the load is larger than the limitation
FailSafeInverter and meter communication failure -FailSafe is enabledTroubleshoot communication between the inverter and meter. See the article FailSafe on how to disable this setting if you do not want it enabled.
MET_Comm-FAILInverter and external (Acrel) meter are not communicatingMake sure the RS485 between the inverter and meter is installed properly. If no meter is installed, change to "No Meter"
CAN_Comm_FAILBattery CAN FailCheck if the CAN cable is correctly connected or the cables are broken/loosen
DSP_Comm_FAILDSP COM FailRestart the inverter
Alarm-BMSBattery BMS AlarmRetart the battery, if fault still exists, please contact battery manufacturer or installer 
BAT_Comm-FAILNo communication between the inverter and battery OR the wrong battery is selectedCheck the RS485 or CAN wire between the inverter and battery. Verify that the correct battery has been selected in the Battery Select submenu of Advanced Settings
LG-DDC-OVLG Battery overvoltage Turn both battery breaker off and then back on again after ten minutes. 
LG-Comm-FAILLG Battery Com FailCheck the RS485 cable of LG battery. Ensure it is correctly connected without broken insulation
LG-BMS-FaultLG BMS is having it's own fault and the inverter is just relaying the messageRestart the battery. If the fault still exists, contact LG for assistance


V
Victor is the author of this solution article.

Did you find it helpful? Yes No

Send feedback
Sorry we couldn't be helpful. Help us improve this article with your feedback.