User Defined 480V-A Grid Standard

User Defined 480V-A Grid Standard

ParameterValueValue Phase to GroundDescription
OV-G-V1528V304vLevel 1 Phase to Phase over voltage trip set point
OV-G-V1 - T
1s
Duration of grid over voltage trip point
OV-G-V2
576V332vLevel 2 Phase to Phase over voltage trip set point
OV-G-V2 - T
.16s
Duration of grid over voltage trip point
UN-G-V1422.2V243VLevel 1 Phase to Phase under voltage trip set point
UN-G-V1 - T
2s
Duration of grid under voltage trip point
UN-G-V2
288V166VLevel 2 Phase to Phase under voltage trip set point
UN-G-V2 - T
.16s
Duration of grid under voltage trip point
OV-G-F160.5Hz
Level 1 Grid over frequency trip set point
OV-G-F1 - T
2s    
Duration of grid over frequency trip set point
OV-G-F2
62Hz
Level 2 Grid over frequency trip set point
OV-G-F2 - T
.16s
Duration of grid over frequency trip set point
UN-G-F159.5Hz
Level 1 Grid under frequency trip set point
UN-G-F1- T
2s
Duration of grid under frequency trip set point
UN-G-F2
57Hz
Level 2 Grid under frequency trip set point
UN-G-F2 - T
.16s
Duration of grid under frequency trip set point